Produktbeschreibung
Used-Power Transformer, Hyundai, Type TL-0596, Vector Group Symbol YNyn0dl. Type of cooling: ONAN/ONAF/ONAF, 3 phase, standard CSA-C88-M90, 90 hz. Max temp rise winding/oil 65/65 deg C. HV rated capacity 70/93.1/116.2 MVA. Rated voltage 260 KV, rated current 155/206/258 A, BIL (line neutral) 950/95 KV. LV rated capacity 70/93.1/116.2 MVA, rated voltage 72 KV, rated current 561/746/931 A, BIL (line neutral) 350/95 KV. TV rated capacity 21/28/35 MVA. Rated voltage 13.8 kv, rated current 878/1171/1464 A, BIL (line neutral) 110 kv. % impedance at 85 deg C on 70 MVA (ONAN) base: HV-LV 8.99%, HV-TV 10.81%, LV-TV 5.65%. Capacity at 0 deg C ambient temp HV 87.5/110.5/137.9 MVA LV 87.5/110.5/137.9 MVA, TV 26.2/33.2/41.5 MVA. Dynamic earthquake withstand: horizontal 0.3 G, vertical 0.24 G. Sound level at 116.2 MVA base 83 db. Type of insulating oil: volt ESSO 35. Material of conductor: copper. Tank withstand pressure 1.0 kg/cm2, core and coil (untanking) 81,500 kg, tank and fittings 45,500 kg. Quantity of oil: 45,500 kg. Manufactured 1999.